PRA number
2017/15864
Published date
Product description
230DRAQTP: Meter Boxes - Metal, Queensland Type, 21 Module switchboard and meter box (suitable for temporary supply AS/NZS3012 compliant).
Meter box - 690H x 470W x 290D.
Internal Meter Panel - 480H x 460W.
230DRAQ: Meter Boxes - Metal, Queensland Type, 21 Module switchboard and meter box.
Meter box - 690H x 470W x 290D.
Internal Meter Panel - 480H x 460W.
230DRAVL: Vic Meter Box with 21 Module Enclosure and Coin Lock.
Meter box - 690H x 470W x 290D.
Internal Meter Panel - 380H x 400W.
230DRAT: Meter Boxes - Metal, Tasmanian Type, Meter box with DIN rail.
Meter box - 690H x 470W x 290D.
Internal Meter Panel - 480H x 460W.
230DRAQ: Meter Boxes - Metal, Queensland Type, 21 Module switchboard and meter box.
Meter box - 690H x 470W x 290D.
Internal Meter Panel - 480H x 460W.
230DRAVL: Vic Meter Box with 21 Module Enclosure and Coin Lock.
Meter box - 690H x 470W x 290D.
Internal Meter Panel - 380H x 400W.
230DRAT: Meter Boxes - Metal, Tasmanian Type, Meter box with DIN rail.
Reasons the product is recalled
The conductive parts of the enclosure may not be effectively earthed, as the earth cable supplied in the meter boxes was not manufactured to specifications and is not compliant to standards.
The hazards to consumers
This could result in a potential electric shock if a live wire were to come into contact with the enclosure.
What consumers should do
If consumers have had a Clipsal meter box installed at their home or premises, that was purchased between 18th April 2016 and 17 August 2016, they may have an affected product installed. Consumers should contact Clipsal on 1300 369 233 for further instructions.
Supplier
Schneider Electrical President Systems Limited
Where the product was sold
Queensland
Tasmania
Victoria
Dates available for sale
-
Recall advertisements and supporting documentation
Responsible regulator
Office of the technical regulator (SA) is the responsible regulator for this recall.