Total Tools—Saber Generator
What are the defects?
Manufactured with a Multiple Earth Neutral (MEN) link between the neutral & earth without a residual Current Device (RCD), which is non-compliant with safety clause 6 of AS2790 Electricity generating sets. In addition, the Circuit Breaker Switch for Equipment (CBE) is single pole, which is non-compliant with safety clause 6.1.4.
What are the hazards?
If a fault occurs in the unit or equipment there is a possibility of electric shock.
What should consumers do?
Cease using the product immediately. Customers should return their unit to the Total Tools store where purchased for rectification of the defect.
Supplier
Traders who sold this product
37 Total Tools franchised stores
Where the product was sold
Australian Capital Territory
New South Wales
Queensland
South Australia
Victoria
Recall advertisements and supporting documentation
Responsible regulator
Energy Safe (VIC) is the responsible regulator for this recall.
Product category