Clipsal—WHB 355 Weathershield—IP66, Switch 440V 55A triple pole units

PRA number

2008/9956

Published date

Product description

Model numbers: WHB355,RG. WHB355,RW. WHB355/32,RG. The product is primarily used in industrial and commercial applications, to control and isolate energy. The WHT20-21 bases and associated WHB 355 Weathershield switch manufactured since July 2007 are affected.
Clipsal WHB 355 Weathershield - IP66, Switch 440V 55A triple pole units
Identifying features
N/A

Other identifying numbers

N/A

What are the defects?

It has been determined that upon the change to a new moulding tool, the WHT20-21 base pockets are not to specification i.e. they are too deep. This allows for excessive movement of the terminal in the pocket and for the potential for the circuit to close when the switch is in the 'OFF' position.

What are the hazards?

Electrocution

What should consumers do?

Customers are advised to ensure that all electrical circuits, where the WHB 355 Weathershield switch is installed are fully disconnected (using voltage detectors) before conducting any electrical installation or maintenance work.

Supplier

Clipsal Australia Pty Limited

Where the product was sold

Nationally

Responsible regulator

Australian Competition and Consumer Commission is the responsible regulator for this recall.