Schneider Electric (Australia) Pty Limited—230DRAS1MI and 230DRAS2MI Meter Boxes

PRA number

2015/14842

Published date

Product description

230DRAS1MI Meter Boxes - Metal, South Australian Type, 21 Module switchboard and single meter box, Complete with 230MIC163, H612 x W505 x D260mm(overall dimensions), Meter Panel Dimensions: H350mm x W350mm

230DRAS2MI Meter Boxes - Metal, South Australian Type, 21 Module switchboard and multiple meter box, Complete with 230MIC163, H805 x W505 x D260mm (overall dimensions), Meter Panel Dimensions: H550mm x W350mm
Slide1
Identifying features
Product Sold between January 2015 and July 2015 Product with a date code between S12014480001 and S12015252308 for 230DRAS1MI, S22014480001 and S22015100570 for 230DRAS2MI can be affected

Other identifying numbers

Product Sold between January 2015 and July 2015

Product with a date code between S12014480001 and S12015252308 for 230DRAS1MI, S22014480001 and S22015100570 for 230DRAS2MI can be affected

Reasons the product is recalled

4CB163/6 Meter Isolator fitted in the 230DRAS Meter Box, may have the incorrect screw fitted on the lockout plate, causing electrical contact between the screw and metal bobbin assembly.

The hazards to consumers

A screw on the side of the meter isolator may be electrically live. There is a risk of electric shock if contact is made with this screw.

What consumers should do

If consumers have had electrical installation work carried out at their home or premises from January 2015 to July 2015 they may have had an affected product installed. They should contact Clipsal Direct on Tel # (1300 733 907) with full details so a replacement meter isolator can be organised as soon as possible. Consumers should not attempt to inspect or assess products themselves. For further information on the recall, and on how customers can organise a replacement circuit breaker please see www.clipsal.com/230DRASrecall.

Traders who sold this product

Electrical Wholesalers

Where the product was sold

South Australia

Dates available for sale

-

Recall advertisements and supporting documentation

Recall advertisement

Responsible regulator

Office of the Technical Regulator (SA) is the responsible regulator for this recall.