Product description
This recall notice is issued by the Minister for Justice and Attorney-General pursuant to Section 122 of the Australian Consumer Law (Qld)
The products are DC solar power isolator switches forming part of the Blueline solar power system.
          The products are DC solar power isolator switches forming part of the Blueline solar power system.
See a list of details to help identify the product
Reason the product is recalled
High temperature can occur at the internal switch plate, causing the contacts to spread and the polymer support plate to degrade.
The hazards to consumers
This poses a risk of arcing and eventual catastrophic failure, resulting in fire.
What consumers should do
Owners should immediately shut down the PV system following the standard shutdown procedure.
Note that Blueline Solar Pty Ltd is now insolvent.
If a consumer suspects they have one of the affected units, they should have an electrician inspect and replace the DC isolators.
Note that Blueline Solar Pty Ltd is now insolvent.
If a consumer suspects they have one of the affected units, they should have an electrician inspect and replace the DC isolators.
Details to help identify the product
Supplier running the recall
Blue Line Solar pty ltd
Who sold the product
The Blueline solar system was sold to:
• Australian Institute of Renewable Energy (AIRE);
• Queensland Renewable Energy (QRE);
• Polaris Solar;
• Darwin Solar;
• Combined Solar;
• United Renewable Energy;
• Genlux;
• ACT Renewable Energy; and
• Capital Solar
• Australian Institute of Renewable Energy (AIRE);
• Queensland Renewable Energy (QRE);
• Polaris Solar;
• Darwin Solar;
• Combined Solar;
• United Renewable Energy;
• Genlux;
• ACT Renewable Energy; and
• Capital Solar
Identifying product features
Model numbers are AV/DC4P25A and AV/DC4P25AUT
Identifying numbers
Other identifying numbers
Model numbers are AV/DC4P25A and AV/DC4P25AUT
Where the product was sold
Nationally
Responsible regulators
Regulators are established or appointed by government. They enforce regulations and rules.
Quote PRA number 2014/14332 when contacting a regulator about this recall.
Recall and remedy questions
Contact the Australian Competition and Consumer Commission if you have:
- a question about the remedy being offered to you by the business that is responsible for managing this recall, or
 - concerns about the way the business is managing this recall.
 

Product questions
Speak to the Electrical Safety Office (QLD) if you have a question about the reason the product is recalled or the hazards to consumers.