Product description

The affected cylinders are "Worthington" 80 litre cylinders.
They are readily identified as they are approximately 90mm shorter than the 200 Inergen cylinders previously supplied. They also have a unique cylinder number stamped on the cylinder neck in 10mm high number just below the tranport cap.
The cylinders were filled between 1 May 2006 and 13 July 2006.

See a list of details to help identify the product

Reason the product is recalled

During filling of new 200 bar cylinders, several crates of cylinders were inadvertently contaminated prior to filling as water was permitted to enter the cylinder through an open fill adaptor fitted to the Inergen CV98 valve.
The water in the cylinder could, after several months, corrode the Safety Burst Disc on the valve giving rise to the potential for premature rupture of the disk at normal ambient temperatures.

What consumers should do

Contact your nearest Wormald Branch.

Details to help identify the product

Supplier running the recall

Tyco Group—Australia/New Zealand

Identifying product features

Cylinder Numbers: ALA-TY 06690 - ALA-TY 06737 ALA-TY 06770 - ALA-TY 06785 ALA-TY 06883 - ALA-TY 06898 ALA-TY 06946 - ALA-TY 6961 ALA-TY 06978 - ALA-TY 07041 ALA-TY 07122 - ALA-TY 07137 ALA-TY 07362 - ALA-TY 07393 ALA-TY 07427 - ALA-TY 07473 ALA-TY 07522 - ALA-TY 07537 ALA-TY 07554 - ALA-TY 07569 ALA-TY 07586 - ALA-TY 07617

Identifying numbers

Other identifying numbers

Cylinder Numbers: ALA-TY 06690 - ALA-TY 06737ALA-TY 06770 - ALA-TY 06785ALA-TY 06883 - ALA-TY 06898ALA-TY 06946 - ALA-TY 6961ALA-TY 06978 - ALA-TY 07041ALA-TY 07122 - ALA-TY 07137ALA-TY 07362 - ALA-TY 07393ALA-TY 07427 - ALA-TY 07473ALA-TY 07522 - ALA-TY 07537ALA-TY 07554 - ALA-TY 07569ALA-TY 07586 - ALA-TY 07617

Where the product was sold

Nationally

Responsible regulators

Regulators are established or appointed by government. They enforce regulations and rules.

Quote PRA number 2007/9367 when contacting a regulator about this recall.

Recall and remedy questions

Contact the Australian Competition and Consumer Commission if you have:

  • a question about the remedy being offered to you by the business that is responsible for managing this recall, or
  • concerns about the way the business is managing this recall.