Product description
The affected cylinders are "Worthington" 80 litre cylinders.
They are readily identified as they are approximately 90mm shorter than the 200 Inergen cylinders previously supplied. They also have a unique cylinder number stamped on the cylinder neck in 10mm high number just below the tranport cap.
The cylinders were filled between 1 May 2006 and 13 July 2006.
They are readily identified as they are approximately 90mm shorter than the 200 Inergen cylinders previously supplied. They also have a unique cylinder number stamped on the cylinder neck in 10mm high number just below the tranport cap.
The cylinders were filled between 1 May 2006 and 13 July 2006.
See a list of details to help identify the product
Reason the product is recalled
During filling of new 200 bar cylinders, several crates of cylinders were inadvertently contaminated prior to filling as water was permitted to enter the cylinder through an open fill adaptor fitted to the Inergen CV98 valve.
The water in the cylinder could, after several months, corrode the Safety Burst Disc on the valve giving rise to the potential for premature rupture of the disk at normal ambient temperatures.
The water in the cylinder could, after several months, corrode the Safety Burst Disc on the valve giving rise to the potential for premature rupture of the disk at normal ambient temperatures.
What consumers should do
Contact your nearest Wormald Branch.
Details to help identify the product
Supplier running the recall
Tyco Group—Australia/New Zealand
Identifying product features
Cylinder Numbers:
ALA-TY 06690 - ALA-TY 06737
ALA-TY 06770 - ALA-TY 06785
ALA-TY 06883 - ALA-TY 06898
ALA-TY 06946 - ALA-TY 6961
ALA-TY 06978 - ALA-TY 07041
ALA-TY 07122 - ALA-TY 07137
ALA-TY 07362 - ALA-TY 07393
ALA-TY 07427 - ALA-TY 07473
ALA-TY 07522 - ALA-TY 07537
ALA-TY 07554 - ALA-TY 07569
ALA-TY 07586 - ALA-TY 07617
Identifying numbers
Other identifying numbers
Cylinder Numbers: ALA-TY 06690 - ALA-TY 06737ALA-TY 06770 - ALA-TY 06785ALA-TY 06883 - ALA-TY 06898ALA-TY 06946 - ALA-TY 6961ALA-TY 06978 - ALA-TY 07041ALA-TY 07122 - ALA-TY 07137ALA-TY 07362 - ALA-TY 07393ALA-TY 07427 - ALA-TY 07473ALA-TY 07522 - ALA-TY 07537ALA-TY 07554 - ALA-TY 07569ALA-TY 07586 - ALA-TY 07617
Where the product was sold
Nationally
Responsible regulators
Regulators are established or appointed by government. They enforce regulations and rules.
Quote PRA number 2007/9367 when contacting a regulator about this recall.
Recall and remedy questions
Contact the Australian Competition and Consumer Commission if you have:
- a question about the remedy being offered to you by the business that is responsible for managing this recall, or
- concerns about the way the business is managing this recall.